Model: |
HP-MX2 |
Categories: |
Pressure Transmitter |
Description: |
|
|
Intrinsically safe pressure
transmitter for industrial use |
|
|
|
|
Electrical Data |
Max. measuring range |
0…600 mbar, 0…2000 bar |
Overload pressure |
50 mbar…2400 bar(depending on
the Max. measuring range) |
Burst pressure |
150 mbar…3000 bar(depending on
the Max. measuring range) |
Output signal |
4…20 mA |
Supply voltage |
9…27 V |
Response time |
<1 ms |
Accuracy |
≤0.50%(optional 0.25%)(1…2000 bar);
≤1.00%(optional 0.50%)(10…600 mbar) |
Mechanical Data |
Housing |
Stainless steel |
Parts in contact with
the measuring medium |
stainless steel(1…2000 bar),silicon (10…600 mbar) |
Shock resistance |
1000 g |
Vibration resistance |
20 g |
Measuring medium
temperature |
Zone 0: -20℃…+60℃ |
Zone 1: -40℃…+100℃ |
Ambient temperature |
Zone 0: -20℃…+60℃ |
Zone 1: -40℃…+85℃ |
Storage temperature |
Zone 0: -20℃…+120℃ |
Zone 1: -40℃…+125℃ |
Protection |
IP65(special version up to IP69K) |
Connector |
M12×1; MVS/A; MVS/C; Cable * |
Pressure connection |
G 1/4 A, Form E; G1/4 B; G1/2 B; 1/4 NPT * |
Directive ATEX
Type of ignitionprotection
|
Zone 0:II 1G Ex ia IIB T4
II 1G Ex ia T4(only for M12×1)
|
Zone 1:II 2G Ex ia IIC T4
|
Underlying standards |
EN 60079-0, EN 60079-11, EN 60079-14, EN 60079-26
|
*Custom-made adjustments acc. to pressure connections and connecting options are possible. |
[Back] |